Ht-instruments MACROTEST 5035 Manuale Utente Pagina 41

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 80
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 40
MACROTEST 5035
EN - 40
If one cable is not connected to the
network or one phase is absent, the
instrument displays the screen
alongside
0 V
0 V 388 V
If two or more cables of the instrument is
not connected, it displays screen
alongside.
0 V
0 V 0 V
SAVING: The tests can be stored pressing the SAVE key twice
(according to paragraph 5.1).
Black cable=L1 is not connected to one phase of
the installation. Voltage between phase L1 and
phase L2 is null (L1-L2).
Black cable=L1 is not connected to one phase of
the installation. Voltage between phase L3 and
phase L1 is null (L3 - L1).
Black cable= L1
is not connected
to one phase of
the installation.
Voltage between
phase L2 and
phase L3 is not
null (L2- L3).
SAVE
Vedere la pagina 40
1 2 ... 36 37 38 39 40 41 42 43 44 45 46 ... 79 80

Commenti su questo manuale

S.imoim.net 04 Dec 2024 | 14:11:18

Text and images you copy will automatically show hereText and images you copy will automatically show here