MACROTESTG3 - COMBIG3
EN - 48
5.
Press the GO/STOP key or the START key on the
remote lead. During this whole stage, do not disconnect
the measuring leads of the instrument from the system
under test.
In case of positive result (overall earth resistance lower
than the ratio between limit contact voltage and RCD
tripping current), the screen to the side is displayed by
the instrument, which contains the contact voltage
value in the secondary display.
Press the SAVE button or touch the icon to save
the measurement (see § 7.1).
6. In case of negative result (overall earth resistance
higher than the ratio between limit contact voltage and
RCD tripping current), the screen to the side is
displayed by the instrument.
Note the presence of the measurement result of the
contact voltage highlighted in red.
Press the SAVE button or touch the icon to save
the measurement (see § 7.1).